维普中文期刊产品整合服务
共被期刊论文引用了1次 您的检索式:您选中1篇文献正在查看引证文献汇总
    题名 作者 年代 出处 被引量
1VFT PHASE VOLTAGE MEASUREMENT IN THREE-PHASE ENCLOSED GIS显示文摘The measuring of VFT phase voltage in three-phase enclosed GIS is more complex and difficult than in single-phase ones. There are 3 capacitive sensors in the measuring system, the outputs of which are with a linear relation to the three phase voltages. This linear relation is presented with a factorial matrix. Because each capacitive sensor is coupled with the electric field of three phases (A, B, and C), the electric coupling coefficients are introduced. In order to determine the matrix of electric coupling coefficients, the numerical calculation method can be used. From the discussion on two types of three-phase enclosed GIS bus, i.e. standard arrangement and biased arrangement, the dominant electric coupling coefficients are named, which can be simply and approximately calculated by an analytic expression. Finally, as an example, the waveforms of VFT phase voltage generated on a three-phase enclosed GIS bus model are displayed. When a capacitive sensor is located at the ’shortest point’ of phase A (or B, or C), the VFT phase voltage V A (or V B, or V C) can almost be measured by that capacitive sensor alone.Zou Jianhua(邹建华) Yue Ziding(岳子丁) Li Yang(李洋) 2002Academic Journal of Xi'an Jiaotong University2002,,2:1